Assistant Electrical Inspectors in the Electrical Inspectorate - I Paper

Functions of Electrical Inspectorate ... (Paper I)
Date of Examination 07-03-2019

Question1:-Where is the office of Kerala State Electricity Regulatory Commission located?
 A:-Thiruvananthapuram
 B:-Thrissur
 C:-Ernakulam
 D:-Kozhikkodu
 Correct Answer:- Option-A
Question2:-Which of the following is not a general function of Regional Load Despatch Centre?
 A:-Exercise Supervision and control over the Interstate transmission system
 B:-Collect wheeling charges for the energy transmitted
 C:-Keep accounts of the quantity of electricity transmitted
 D:-Monitor Grid operations
 Correct Answer:- Option-B
Question3:-What is the minimum accuracy class of consumer meters at HT premises?
 A:-0.5 S
 B:-0.2 S
 C:-1 S
 D:-0.25 S
 Correct Answer:- Option-A
Question4:-What is the recommended minimum insulation value (in Mega Ohms) for LV three phase installations?
 A:-5
 B:-1
 C:-3
 D:-2
 Correct Answer:- Option-B
Question5:-What is the distance from a 220 kV tower for which permission from the owner of the tower is required for carrying out cutting of soil?
 A:-50 m
 B:-20 m
 C:-30 m
 D:-10 m
 Correct Answer:- Option-D
Question6:-How many years experience in practice of Electrical Engineering is required, besides other qualifications, for a person to be appointed as Chief Electrical Inspector?
 A:-15
 B:-20
 C:-10
 D:-12
 Correct Answer:- Option-B
Question7:-When a 400 kV DC line crosses another 400 kV DC line, what is the minimum clearance to be maintained?
 A:-6.79 m
 B:-4.58 m
 C:-6.04 m
 D:-3.05 m
 Correct Answer:- Option-C
Question8:-What is the spacing between an underground EHT cable and a Telecommunication cable?
 A:-75 cm
 B:-80 cm
 C:-50 cm
 D:-60 cm
 Correct Answer:- Option-D
Question9:-Which Regulation of CEA (Measures relating to Electric Supply and Safety) Regulations, 2010 makes it mandatory for owners of overhead lines to provide Lightning Diverters?
 A:-76
 B:-81
 C:-74
 D:-114
 Correct Answer:- Option-C
Question10:-What is the generally required minimum height of trolley wires of a traction feeder?
 A:-5.5 m
 B:-5.2 m
 C:-6.2 m
 D:-6.5 m
 Correct Answer:- Option-B
Question11:-What is the cumulative solar power capacity that can normally be connected to the LT side of a distribution transformer, in terms of the transformer capacity?
 A:-50%
 B:-25%
 C:-15%
 D:-30%
 Correct Answer:- Option-C
Question12:-When a 66 kV line crosses a 220 kV line, what is the minimum clearance to be maintained?
 A:-6.79 m
 B:-4.58 m
 C:-6.04 m
 D:-3.05 m
 Correct Answer:- Option-B
Question13:-What is the percentage of ruling tariff applicable for 'Off Peak' usage of energy by an HT consumer?
 A:-50
 B:-75
 C:-100
 D:-125
 Correct Answer:- Option-B
Question14:-What is the distance from a substation below which permission from the owner of the substation is required for carrying out blasting of any type?
 A:-300 m
 B:-350 m
 C:-400 m
 D:-450 m
 Correct Answer:- Option-A
Question15:-How much is the fixed charges for an LT-IV industrial consumer having connected load of 15 KW?
 A:-Rs.100
 B:-Rs.80
 C:-Rs.50
 D:-Rs.60
 Correct Answer:- Option-D
Question16:-What is the minimum vertical clearance specified for a building under a 110 kV line?
 A:-4.6 m
 B:-3.7 m
 C:-2.5 m
 D:-4.0 m
 Correct Answer:- Option-A
Question17:-What is the minimum factor of safety for overhead lines on wooden supports?
 A:-1.5
 B:-2.0
 C:-2.5
 D:-3.0
 Correct Answer:- Option-D
Question18:-What is the minimum horizontal clearance for a building adjacent to an LT line?
 A:-2.5 m
 B:-4.6 m
 C:-1.2 m
 D:-3.7 m
 Correct Answer:- Option-C
Question19:-What is the minimum ground clearance for a 400 kV HVDC line?
 A:-8.5 m
 B:-9.4 m
 C:-10.6 m
 D:-7.3 m
 Correct Answer:- Option-B
Question20:-How many joints are allowed in one span of an overhead line?
 A:-1
 B:-4
 C:-2
 D:-3
 Correct Answer:- Option-A
Question21:-What is the clearance above ground level for an LT overhead line along any street?
 A:-6.4 m
 B:-5.8 m
 C:-6.1 m
 D:-5.5 m
 Correct Answer:- Option-D
Question22:-What is the time limit for restoration of supply in case of break down of overhead lines in Rural Areas?
 A:-12 hours
 B:-8 hours
 C:-16 hours
 D:-24 hours
 Correct Answer:- Option-A
Question23:-What is the frequency of periodical inspection of HT installations in the state?
 A:-every year
 B:-once in two years
 C:-once in three years
 D:-once in five years
 Correct Answer:- Option-A
Question24:-What is the rate of Electricity Duty per unit of consumption applicable to HT consumers in the state?
 A:-1.2 paise
 B:-12 paise
 C:-100 paise
 D:-10 paise
 Correct Answer:- Option-D
Question25:-What should be the minimum height to be provided for a passage behind a panel?
 A:-1 m
 B:-1.5 m
 C:-1.6 m
 D:-1.8 m
 Correct Answer:- Option-D
Question26:-What is the time limit for restoration of supply in case of failure of distribution transformer in difficult areas?
 A:-72 hours
 B:-48 hours
 C:-16 hours
 D:-24 hours
 Correct Answer:- Option-B
Question27:-What is the prescribed periodicity for testing of consumers' meters?
 A:-2 years
 B:-3 years
 C:-4 years
 D:-5 years
 Correct Answer:- Option-D
Question28:-Which is the IS for fire fighting systems in substations?
 A:-3646/1966
 B:-3034/1993
 C:-8061/1976
 D:-3043/1987
 Correct Answer:- Option-B
Question29:-What is the clearance above ground level for an LT overhead line along any street?
 A:-5.5 m
 B:-5.8 m
 C:-6.1 m
 D:-6.4 m
 Correct Answer:- Option-A
Question30:-What is the maximum periodicity of inspection of electrical installations?
 A:-4 years
 B:-5 years
 C:-2 years
 D:-1 year
 Correct Answer:- Option-B
Question31:-What is the clearance above ground level for an HT overhead line along any street?
 A:-5.8 m
 B:-5.5 m
 C:-6.1 m
 D:-6.4 m
 Correct Answer:- Option-A
Question32:-When a 110 kV AC line across crosses a 500 KV DC line, what is the minimum clearance to be maintained?
 A:-6.79 m
 B:-7.54 m
 C:-6.04 m
 D:-3.05 m
 Correct Answer:- Option-A
Question33:-Who appoints the chairperson of Consumer Grievance Redressal Forum?
 A:-The State Government
 B:-State electricity Regulatory Commission
 C:-The Licensee
 D:-Public Service Commission
 Correct Answer:- Option-C
Question34:-What is the maximum allowable percentage of Neutral Voltage in a distribution system?
 A:-2
 B:-3
 C:-4
 D:-5
 Correct Answer:- Option-A
Question35:-What is the minimum horizontal clearance for a building adjacent to a 110 kV line?
 A:-2.5 m
 B:-4.6 m
 C:-1.2 m
 D:-2.9 m
 Correct Answer:- Option-D
Question36:-Which Regulation of CEA (Measures relating to Safety and Electric supply) Regulations, 2010 prescribes earth guarding for overhead lines?
 A:-67
 B:-73
 C:-60
 D:-114
 Correct Answer:- Option-B
Question37:-How many years' experience in practice of Electrical Engineering is required, besides other qualifications, for a person to be appointed as Electrical Inspector?
 A:-15
 B:-20
 C:-10
 D:-8
 Correct Answer:- Option-C
Question38:-When a 66 kV line crosses a 110 kV line, what is the minimum clearance to be maintained?
 A:-6.79 m
 B:-4.58 m
 C:-6.04 m
 D:-3.05 m
 Correct Answer:- Option-D
Question39:-When a 220 kV line crosses a 110 kV line, what is the minimum clearance to be maintained?
 A:-4.58 m
 B:-3.05 m
 C:-5.04 m
 D:-2.44 m
 Correct Answer:- Option-A
Question40:-Which is the 'Normal period' of demand for electricity supply specified for the state?
 A:-10:00 hours to 17:00 hours
 B:-08:00 hours to 16:00 hours
 C:-18:00 hours to 22:00 hours
 D:-06:00 hours to 18:00 hours
 Correct Answer:- Option-D
Question41:-What is the minimum horizontal clearance for a building adjacent to an 11 kV line?
 A:-2.5 m
 B:-4.6 m
 C:-3.7 m
 D:-1.2 m
 Correct Answer:- Option-D
Question42:-What is the percentage of ruling tariff applicable for 'Peak period' usage of energy by an HT consumer?
 A:-200
 B:-150
 C:-100
 D:-125
 Correct Answer:- Option-B
Question43:-Which is the IS for Fire Safety of Buildings?
 A:-3837/1976
 B:-1646/1997
 C:-3854/1997
 D:-732/1989
 Correct Answer:- Option-B
Question44:-How much is the connected load above which Energy Conservation Building Code is to be implemented?
 A:-1000 kW
 B:-100 kW
 C:-500 kW
 D:-200 kW
 Correct Answer:- Option-C
Question45:-What is the minimum horizontal clearance for a building adjacent to a 33 kV line?
 A:-2.5 m
 B:-4.6 m
 C:-1.2 m
 D:-2.0 m
 Correct Answer:- Option-D
Question46:-What is the rate of Electricity Duty per unit consumption for Public Lighting in the state?
 A:-10 paise
 B:-12 paise
 C:-0 paise
 D:-20 paise
 Correct Answer:- Option-C
Question47:-What is the allowable variations in voltage on the higher side of HT supply?
 A:-6%
 B:-8%
 C:-9%
 D:-12%
 Correct Answer:- Option-C
Question48:-What is the minimum insulation value (in Mega Ohms) prescribed for HT installations?
 A:-10
 B:-100
 C:-50
 D:-5
 Correct Answer:- Option-D
Question49:-What is the ground clearance for a bare 11 kV line elsewhere other than a street?
 A:-4.6 m
 B:-4.9 m
 C:-5.1 m
 D:-6.4 m
 Correct Answer:- Option-A
Question50:-Which is the 'Peak hours' demand for electricity supply specified for the state?
 A:-10:00 hours to 17:00 hours
 B:-08:00 hours to 16:00 hours
 C:-18:00 hours to 22:00 hours
 D:-06:00 hours to 18:00 hours
 Correct Answer:- Option-C
Question51:-When an 11 kV line crosses another 11 kV line, what is the minimum clearance to be maintained?
 A:-3.05 m
 B:-4.58 m
 C:-6.04 m
 D:-2.44 m
 Correct Answer:- Option-D
Question52:-When a 220 kV AC line crosses a 400 kV DC line, what is the minimum clearance to be maintained?
 A:-6.79 m
 B:-4.58 m
 C:-6.04 m
 D:-3.05 m
 Correct Answer:- Option-C
Question53:-With whom an appeal is to be filed against an order an electricity Inspector?
 A:-Deputy Chief Electrical Inspector
 B:-Chief Electrical Inspector
 C:-State Government
 D:-Central Government
 Correct Answer:- Option-B
Question54:-How much is the Demand Charges per kVA demand per month for an HT 1(A) consumer?
 A:-Rs.300
 B:-Rs.500
 C:-Rs.400
 D:-Rs.600
 Correct Answer:- Option-A
Question55:-Which is the IS for Switches for domestic use?
 A:-732/1989
 B:-2412/1975
 C:-3043/1987
 D:-3854/1997
 Correct Answer:- Option-D
Question56:-Who is the competent authority to appoint Electricity Ombudsman of a state?
 A:-The licensee
 B:-The High Court
 C:-The State Electricity Regulatory Commission
 D:-The Chief Electrical Inspector
 Correct Answer:- Option-C
Question57:-What is the rate of duty applicable for each unit of energy generated for self consumption?
 A:-12 paise
 B:-1.2 paise
 C:-2 paise
 D:-20 paise
 Correct Answer:- Option-B
Question58:-When a 110 kV line crosses another 110 kV line, what is the minimum clearance to be maintained?
 A:-4.58 m
 B:-3.05 m
 C:-6.04 m
 D:-2.44 m
 Correct Answer:- Option-A
Question59:-Who appoints Appellate authority?
 A:-Chief Electrical Inspector
 B:-State Government
 C:-Licensee
 D:-State Electricity Regulatory Commission
 Correct Answer:- Option-B
Question60:-What is the maximum permissible number of 1.5 sq.mm single core cables that may be drawn into 20 mm Rigid non-metallic conduit?
 A:-4
 B:-6
 C:-8
 D:-10
 Correct Answer:- Option-B
Question61:-What is the minimum factor of safety for stay wires?
 A:-1.5
 B:-2.0
 C:-2.5
 D:-3.0
 Correct Answer:- Option-C
Question62:-What is the minimum cross sectional area of a trolley wire?
 A:-0.5 sq.mm
 B:-1.0 sq.mm
 C:-1.5 sq.mm
 D:-2.0 sq.mm
 Correct Answer:- Option-A
Question63:-What is the minimum vertical clearance for a building under a 220 kV line?
 A:-2.5 m
 B:-4.6 m
 C:-5.5 m
 D:-2.0 m
 Correct Answer:- Option-C
Question64:-Who is the ex-officio Secretary of Kerala State Electricity Licensing Board?
 A:-The Deputy Chief Electrical Inspector of Chief Electrical Inspectorate
 B:-The Power Secretary
 C:-Additional Chief Electrical Inspector
 D:-The Senior most Electrical Inspector
 Correct Answer:- Option-A
Question65:-What is the mandatory clearance to be provided in front of an LT panel?
 A:-75 cm
 B:-80 cm
 C:-90 cm
 D:-100 cm
 Correct Answer:- Option-D
Question66:-What is the minimum vertical clearance specified for a building under an LT line?
 A:-4.6 m
 B:-3.7 m
 C:-2.5 m
 D:-4.0 m
 Correct Answer:- Option-C
Question67:-What is the time limit for restoration of supply in case normal fuse off calls in urban areas?
 A:-8 hours
 B:-10 hours
 C:-6 hours
 D:-12 hours
 Correct Answer:- Option-C
Question68:-What is the minimum vertical clearance specified for a building under an HT line?
 A:-4.6 m
 B:-3.7 m
 C:-2.5 m
 D:-4.0 m
 Correct Answer:- Option-B
Question69:-How much is the Diversity Factor for domestic Lighting?
 A:-1
 B:-2
 C:-1.5
 D:-0.75
 Correct Answer:- Option-C
Question70:-Which of the following is not under the administrative control of the Department of Electrical Inspectorate?
 A:-Kerala State Electricity Licensing Board
 B:-Kerala State Electricity Board Ltd.
 C:-The Meter Testing and Standards Laboratory
 D:-Kerala State Cinema operators Examination Board
 Correct Answer:- Option-B
Question71:-Which of the following 'IS' give recommendations on safety procedures and practices in Electricity work?
 A:-5216/1982
 B:-3034/1993
 C:-3043/1987
 D:-7689/1989
 Correct Answer:- Option-A
Question72:-What is the minimum vertical clearance specified for a building under a 66 kV line?
 A:-4.6 m
 B:-3.7 m
 C:-2.5 m
 D:-4.0 m
 Correct Answer:- Option-D
Question73:-How many months is the maximum validity normally for a temporary connection?
 A:-12
 B:-3
 C:-9
 D:-6
 Correct Answer:- Option-A
Question74:-What is the maximum height at which the Emergency Switch for disconnecting supply to a Multi-storied building has to be located?
 A:-1.5 m
 B:-1.6 m
 C:-1.7 m
 D:-1.8 m
 Correct Answer:- Option-C
Question75:-What is the maximum connected load that can be connected to a 415 V supply?
 A:-50 kVA
 B:-200 kVA
 C:-100 kVA
 D:-5 kVA
 Correct Answer:- Option-C
Question76:-What is the estimated load, as per norms, for each 10 square meter of constructed area in a commercial installation?
 A:-1000 W
 B:-1500 W
 C:-2000 W
 D:-2500 W
 Correct Answer:- Option-B
Question77:-Which section of Electricity Act 2003 contains Provisions relating to Safety and Electricity Supply?
 A:-33
 B:-63
 C:-83
 D:-53
 Correct Answer:- Option-D
Question78:-Which of the following is not a general function of Central Electricity Regulatory Commission?
 A:-Build and Operate power generating stations
 B:-Determine tariff for inter state transmission of electricity
 C:-Regulate inter state transmission of Electricity
 D:-Specify Grid code having regard to Grid standards
 Correct Answer:- Option-A
Question79:-What is the maximum Contract Demand allowed for a consumer availing 11 kv supply?
 A:-500 kVA
 B:-100 kVA
 C:-1000 kVA
 D:-3000 kVA
 Correct Answer:- Option-D
Question80:-What is the percentage of permissible loading unbalance between phases of a Low voltage three phase consumer?
 A:-10
 B:-12
 C:-8
 D:-5
 Correct Answer:- Option-D
Question81:-When a 220 kV line crosses another 220 kV line, what is the minimum clearance to be maintained?
 A:-3.05 m
 B:-4.58 m
 C:-6.04 m
 D:-2.44 m
 Correct Answer:- Option-B
Question82:-How many days' notice is to be served to a consumer for disconnection of supply for non-payment of dues?
 A:-15
 B:-7
 C:-30
 D:-10
 Correct Answer:- Option-A
Question83:-Which section of Electricity Act 2003, empowers formation of State Electricity Regulatory Commission
 A:-82
 B:-42
 C:-62
 D:-72
 Correct Answer:- Option-A
Question84:-Who appoints the Appellate Tribunal for Electricity?
 A:-State Government
 B:-State Electricity Regulatory Commission
 C:-Central Government
 D:-Central Electricity Regulatory Commission
 Correct Answer:- Option-C
Question85:-What is the maximum Contract Demand allowed for a consumer availing 33 kV supply?
 A:-5000 kVA
 B:-10000 kVA
 C:-15000 kVA
 D:-12000 kVA
 Correct Answer:- Option-D
Question86:-Who is the Appropriate Authority for implementing Quality control Orders for electrical goods in the State?
 A:-State Electricity Regulatory Commission
 B:-Secretary, Industries Department
 C:-Chief Electrical Inspector
 D:-Chief Secretary
 Correct Answer:- Option-C
Question87:-What is the maximum Contract Demand allowed for a consumer availing 110 kV supply?
 A:-40000 kVA
 B:-10000 kVA
 C:-15000 kVA
 D:-30000 kVA
 Correct Answer:- Option-A
Question88:-Which Section of Electricity Act 2003 contains provision for establishing National Load Despatch Centre?
 A:-34
 B:-39
 C:-26
 D:-56
 Correct Answer:- Option-C
Question89:-When an 11 kV line crosses a 110 kV line, what is the minimum clearance to be maintained?
 A:-4.58 m
 B:-3.05 m
 C:-6.04 m
 D:-2.44 m
 Correct Answer:- Option-B
Question90:-What is the maximum span allowed for a Low Voltage overhead line at a road crossing?
 A:-65 m
 B:-80 m
 C:-70 m
 D:-75 m
 Correct Answer:- Option-A
Question91:-What is the maximum number of full time members in Central Electricity Authority?
 A:-6
 B:-7
 C:-9
 D:-8
 Correct Answer:- Option-D
Question92:-What is the Average Service Availability Index (ASAI) for rural areas?
 A:-97
 B:-97.5
 C:-98
 D:-98.5
 Correct Answer:- Option-B
Question93:-What is the clearance above ground level for an HT overhead line across any street?
 A:-5.5 m
 B:-5.8 m
 C:-6.1 m
 D:-6.4 m
 Correct Answer:- Option-C
Question94:-Which is the IS for earthing practices?
 A:-3646/1992
 B:-7662/1974
 C:-3043/1987
 D:-8884/1978
 Correct Answer:- Option-C
Question95:-What is the permissible voltage drop at the end of a feeder cable?
 A:-4%
 B:-5%
 C:-10%
 D:-6%
 Correct Answer:- Option-B
Question96:-How much is the approved power rating of a 16 A socket outlet?
 A:-800 W
 B:-1600 W
 C:-500 W
 D:-1000 W
 Correct Answer:- Option-D
Question97:-How many service tapings can be taken off a support of an LT overhead line?
 A:-10
 B:-6
 C:-8
 D:-4
 Correct Answer:- Option-D
Question98:-What is the clearance above ground level for an LT overhead line across any street?
 A:-5.5 m
 B:-6.1 m
 C:-5.8 m
 D:- 6.4 m
 Correct Answer:- Option-C
Question99:-How many times the normal current is the permissible starting current of a 7.5 kW motor?
 A:-5
 B:-3
 C:-6
 D:-4
 Correct Answer:- Option-B
Question100:-What is the minimum horizontal clearance for a building adjacent to a 66 kV line?
 A:-2.3 m
 B:-4.6 m
 C:-1.2 m
 D:-3.7 m
 Correct Answer:- Option-A