04-09-2019 Assistant Electrical Inspectors Test – Functions of Electrical Inspectorate ….(Paper I)

 FINAL ANSWER KEY 

Paper: Funtions of Electrical Inspectorate ... (Paper I) 

Date of 

Examination 

04-09-2019 

Question1:-The appointment of Electrical Inspector is governed by ____________ section of the Electricity Act 2003.         A:-161 

        B:-162 

        C:-126 

        D:-144 

        Correct Answer:- Option-B 

Question2:-National Load Despatch Centre is established under _____________ section of the Electricity Act 2003.         A:-Subsection (1) of section 27 

        B:-Subsection (2) of section 29 

        C:-Subsection (1) of section 26 

        D:-Subsection (4) of section 28 

        Correct Answer:- Option-C 

Question3:-As per which Regulation of CEA... safety regulations 2010, designating of person(s) are made to operate and carry out the work on the Electrical Lines and apparatus 

        A:-7 

        B:-19 

        C:-3 

        D:-34 

        Correct Answer:- Option-C 

Question4:-Regulation 24 of CEA... safety regulations 2010 insists 

        A:-Distinction of different circuits 

        B:-Earthing systems 

        C:-Load sharing 

        D:-Deposit of maps 

        Correct Answer:- Option-A 

Question5:-Electrical safety officer is designated as per _______________ regulation of CEA... safety regulations 2010.         A:-5 

        B:-12 

        C:-31 

        D:-48 

        Correct Answer:- Option-A 

Question6:-Which regulation of CEA... safety regulations 2010 insists periodical inspection and testing of installations?         A:-63 

        B:-32 

        C:-14 

        D:-30 

        Correct Answer:- Option-D 

Question7:-As per ____________ regulation of CEA... Safety Regulations 2010, the consumer shall take precautions for safe custody of the equipments on his premises belonging to the supplier. 

        A:-16(3) 

        B:-13(3) 

        C:-31(1) 

        D:-46(5) 

        Correct Answer:- Option-B 

Question8:-Which regulation of CEA... Safety Regulations 2010 governs the Handling of supply lines and apparatus?         A:-12 

        B:-50

        C:-19 

        D:-65 

        Correct Answer:- Option-C 

Question9:-The validity of scheme approval issued by Electrical Inspectorate Department is 

        A:-2 years 

        B:-5 years 

        C:-4 years 

        D:-3 years 

        Correct Answer:- Option-A 

Question10:-Regulation 36 of CEA... Safety Regulations 2010 is applicable to the buildings having height 

        A:-15 metres 

        B:-more than 15 metres 

        C:-more than 16 metres 

        D:-10.5 metres 

        Correct Answer:- Option-B 

Question11:-Regulation ______________ of CEA... Safety Regulations 2010 insisting electrical contractor license for electrical installation work.         A:-32 

        B:-43 

        C:-66 

        D:-29 

        Correct Answer:- Option-D 

Question12:-Which Regulation of CEA... safety regulation 2010 governs the actions to be done if a leakage on consumer's premise is suspected?         A:-11 

        B:-55 

        C:-34 

        D:-72 

        Correct Answer:- Option-C 

Question13:-Notice of accidents to Electrical Inspector is insisted as per ____________ section of the The Electricity Act - 2003.         A:-161 

        B:-165 

        C:-162 

        D:-156 

        Correct Answer:- Option-A 

Question14:-As per which section of the Electricity Act 2003 Central Electricity Authority achieve powers to make regulations         A:-176 

        B:-177 

        C:-181 

        D:-185 

        Correct Answer:- Option-B 

Question15:-The Electricity Act 2003 is not applicable to the state 

        A:-Assam 

        B:-Meghalaya 

        C:-Jammu and Kashmir 

        D:-Punjab 

        Correct Answer:- Option-C 

Question16:-Section 70 of the Electricity Act - 2003 is related to the constitution of 

        A:-Central Regulatory Commission 

        B:-State Regulatory Commission 

        C:-Central Electricity Authority 

        D:-State Electricity Board

        Correct Answer:- Option-A 

Question17:-National Electricity Policy Plan insisted in ____________ section of the Electricity Act 2003. 

        A:-3 

        B:-13 

        C:-52 

        D:-40 

        Correct Answer:- Option-A 

Question18:-The electricity supply code is insisted in _____________ section of The Electricity Act 2003. 

        A:-42 

        B:-48 

        C:-74 

        D:-50 

        Correct Answer:- Option-D 

Question19:-The electrical system setup to generate power and distribute electricity in a specified area without connection to the grid is named as         A:-stand by system 

        B:-cogeneration system 

        C:-independent system 

        D:-stand alone system 

        Correct Answer:- Option-D 

Question20:-Non-discriminatory provision for the use of transmission lines or similar facilities by another licensee or consumer engaged in generation of electricity is termed as 

        A:-power access 

        B:-wheeling 

        C:-inter access 

        D:-open access 

        Correct Answer:- Option-D 

Question21:-State Load despatch centre established under ____________ section of The Electricity Act 2003. 

        A:-Subsection 3 of section 26 

        B:-Subsection 1 of section 33 

        C:-Subsection 1 of section 31 

        D:-Subsection 2 of section 32 

        Correct Answer:- Option-C 

Question22:-Control and transmission of electricity is referred in which section of the Electricity Act 2003 

        A:-Section 58 

        B:-Section 54 

        C:-Section 67 

        D:-Section 101 

        Correct Answer:- Option-B 

Question23:-Provision as to the opening up of streets, railways etc. detailed in ______________ section of the Electricity Act 2003.         A:-99 

        B:-110 

        C:-67 

        D:-163 

        Correct Answer:- Option-C 

Question24:-The class of CT to be used by an HT consumer in TOD meter, as per current guideline is ______________.         A:-0.25 

        B:-0.2 

        C:-0.5 

        D:-0.55 

        Correct Answer:- Option-A 

Question25:-Which Regulation of CEA... Safety Regulation - 2010 governs the cutting of soil near a transmission tower?

        A:-75(2) 

        B:-73(3) 

        C:-65(3) 

        D:-27(1) 

        Correct Answer:- Option-C 

Question26:-For over voltage protection of transformer, the tripping shall be given normally to 

        A:-secondary side 

        B:-both primary side and secondary side 

        C:-primary side 

        D:-none of the abve 

        Correct Answer:- Option-C 

Question27:-The minimum size of copper wire used for electrical wiring is 

        A:-`"1.5 mm^2"` 

        B:-`"0.75 mm^2"` 

        C:-`"2.5 mm^2"` 

        D:-`"4 mm^2"` 

        Correct Answer:- Option-A 

Question28:-The current density of steel (GI) taken for earthing design is 

        A:-`"118 A/mm^2"` 

        B:-`"73 A/mm^2"` 

        C:-`"46 A/mm^2"` 

        D:-`"100 A/mm^2"` 

        Correct Answer:- Option-C 

Question29:-The new IS/IEC code for lightining protection is 

        A:-5790 

        B:-9968 

        C:-2082 

        D:-62305 

        Correct Answer:- Option-D 

Question30:-The minimum vertical clearance required for a building under an existing 200 KV overhead line is         A:-4.6 metres 

        B:-5.5 metres 

        C:-4 metres 

        D:-7.3 metres 

        Correct Answer:- Option-B 

Question31:-Functions and Duties of Central Electricity Authority is envisaged in ____________ section of The Electricity Act 2003.         A:-176 

        B:-73 

        C:-35 

        D:-87 

        Correct Answer:- Option-B 

Question32:-Provision relating to safety and electricity supply measures specified in which section of the Electricity Act 2003         A:-16 

        B:-94 

        C:-180 

        D:-53 

        Correct Answer:- Option-D 

Question33:-To determine the tariff for electricity is a function of _________________. 

        A:-State Regulatory Commission 

        B:-Central Regulatory Commission

        C:-Distribution Licensee 

        D:-Transmission Licensee 

        Correct Answer:- Option-A 

Question34:-Appellate Tribunal for Electricity is established under ______________ section of the Electricity Act 2003.         A:-65 

        B:-110 

        C:-7 

        D:-154 

        Correct Answer:- Option-B 

Question35:-Duration of fault current for earthing design of HT installation is taken as 

        A:-40 milli seconds 

        B:-3 seconds 

        C:-1.5 seconds 

        D:-2 seconds 

        Correct Answer:- Option-B 

Question36:-Indian standard 'guide for electrical layout is residential buildings' is 

        A:-4648 

        B:-3151 

        C:-6381 

        D:-732 

        Correct Answer:- Option-A 

Question37:-A Restricted Earth Fault Relay usually represented by the device designation number 

        A:-59 

        B:-44 

        C:-46 

        D:-64 

        Correct Answer:- Option-D 

Question38:-Distance protection relay is applicable to 

        A:-Power transformers 

        B:-Generators 

        C:-Transmission lines 

        D:-HV motors 

        Correct Answer:- Option-C 

Question39:-An on-grid solar power plant essentially requires 

        A:-Earth Fault Protection 

        B:-Differential Protection 

        C:-Overvoltage protection 

        D:-Anti islanding protection 

        Correct Answer:- Option-D 

Question40:-Maximum number of members to be appointed in the governing council of Bureau of Energy Efficiency is         A:-20 

        B:-26 

        C:-30 

        D:-15 

        Correct Answer:- Option-B 

Question41:-Which section of the Energy Conservation Act - 2001 governs the powers of central government to facilitate and enforce efficient use of energy and its conservation? 

        A:-14 

        B:-3 

        C:-8 

        D:-12

        Correct Answer:- Option-A 

Question42:-Regulation 32 of CEA... Safety Regulations - 2010 governs the installation and testing of 

        A:-Motors 

        B:-Power transformers 

        C:-Generating units including renewable sources 

        D:-EHT lines 

        Correct Answer:- Option-C 

Question43:-Who is making the Kerala Electricity Supply Code? 

        A:-KSEBL 

        B:-State Government 

        C:-Central Government 

        D:-KSERC 

        Correct Answer:- Option-D 

Question44:-The Kerala State Electricity Supply Code 2014 made under Section 50 read with section __________ of the Electricity Act 2003 and all other powers enabling in this behalf. 

        A:-181 

        B:-129 

        C:-172 

        D:-104 

        Correct Answer:- Option-A 

Question45:-The voltage specified as extra high voltage in Kerala Electricity Supply Code - 2014 is the voltage exceeding         A:-11 KV 

        B:-66 KV 

        C:-110 KV 

        D:-33 KV 

        Correct Answer:- Option-D 

Question46:-The low tension consumed specified in Kerala Electricity Supply Code - 2014 is a consumer availing electricity at voltage         A:-230 V 

        B:-415 V 

        C:-Voltage not exceeding 1000 V 

        D:-Voltage not exceeding 11 kV 

        Correct Answer:- Option-C 

Question47:-Regulation that governs the tapping of service lines from overhead lines is 

        A:-47 

        B:-71 

        C:-65 

        D:-18 

        Correct Answer:- Option-B 

Question48:-Height of stay insulator from ground level shall not be less than _____________. 

        A:-5 metres 

        B:-3 metres 

        C:-7 metres 

        D:-4 metres 

        Correct Answer:- Option-B 

Question49:-The minimum statutory horizontal clearance required between a building an existing 110 kV overhead line shall be         A:-3.7 m 

        B:-2.6 m 

        C:-2.9 m 

        D:-4.6 m 

        Correct Answer:- Option-C 

Question50:-All generators with rating ______________ and above shall be protected against earth fault or leakage.

        A:-1000 kvA 

        B:-80 kvA 

        C:-125 kvA 

        D:-100 kvA 

        Correct Answer:- Option-D 

Question51:-Which regulation of CEA... Safety Regulation - 2010 insist relevant tests for electrical installations exceeding 650 V which has been disconnected for six months or more before reconnection? 

        A:-46(3) 

        B:-35(2) 

        C:-23(3) 

        D:-30(3) 

        Correct Answer:- Option-A 

Question52:-Regulation of CEA... Regulation - 2010 allowing deviations by central/state government is 

        A:-115 

        B:-116 

        C:-76 

        D:-67 

        Correct Answer:- Option-B 

Question53:-Which regulation of CEA Regulation 2010 insist protection against electromagnetic interference? 

        A:-77 

        B:-72 

        C:-68 

        D:-49 

        Correct Answer:- Option-A 

Question54:-As per ____________ regulation of CEA.... Safety Regulation - 2010 no rods, pipes or similar materials shall be brought with in the flash over distance of bare live conductors or lines. 

        A:-63(3) 

        B:-94(2) 

        C:-64(2) 

        D:-46(4) 

        Correct Answer:- Option-C 

Question55:-Which regulation of CEA... Safety Regulation - 2010 insist earth guarding for rendering the line electrically harmless in case it breaks         A:-53 

        B:-73 

        C:-83 

        D:-80 

        Correct Answer:- Option-B 

Question56:-Regulation of CEA...Safety Regulations - 2010 governs the condition of unused overhead lines is 

        A:-5 

        B:-37 

        C:-13 

        D:-75 

        Correct Answer:- Option-D 

Question57:-The minimum depth of laying of an underground cable above 33 kV is 

        A:-1 m 

        B:-1.2 m 

        C:-1.5 m 

        D:-2 m 

        Correct Answer:- Option-B 

Question58:-As per which Regulation of CEA... Safety Regulation 2010, approval by Electrical Inspector is issued for HT electrical installations         A:-43

        B:-32 

        C:-52 

        D:-42 

        Correct Answer:- Option-A 

Question59:-Which Regulation of CEA... Safety Regulations - 2010 insisting the panels to be painted with the description on its identification at front and at rear? 

        A:-82(3) 

        B:-19(6) 

        C:-13(3) 

        D:-115(3) 

        Correct Answer:- Option-B 

Question60:-Which regulation of CEA... Safety Regulations - 2010 insisting the interlocks and protection for use of electricity at voltage exceeding 650 V? 

        A:-79 

        B:-47 

        C:-51 

        D:-45 

        Correct Answer:- Option-D 

Question61:-_____________ of transformers only shall be used for installations inside the residential or commercial buildings.         A:-oil type 

        B:-oil type or dry type 

        C:-dry type 

        D:-none of the above 

        Correct Answer:- Option-C 

Question62:-The percentage impedance of a distribution transformer is generally of the order of 

        A:-5% 

        B:-10% 

        C:-8% 

        D:-13% 

        Correct Answer:- Option-A 

Question63:-Which section of the Electricity Act - 2003 governs the grant of licence 

        A:-23 

        B:-74 

        C:-14 

        D:-121 

        Correct Answer:- Option-C 

Question64:-As per CEA... Safety Regulations - 2010, the permitted number of joints in a span of an overhead line is _______________.         A:-2 

        B:-4 

        C:-3 

        D:-1 

        Correct Answer:- Option-D 

Question65:-Which Regulation of CEA... Safety Regulations - 2010 governs the supply to luminous tube sign installations of voltage exceeding 650 V but not exceeding 33 kV? 

        A:-52 

        B:-20 

        C:-108 

        D:-29 

        Correct Answer:- Option-A 

Question66:-The statutory minimum ground clearance required for a 33 kV overhead line erected across a street is         A:-7.2 m

        B:-6.1 m 

        C:-5.8 m 

        D:-4.6 m 

        Correct Answer:- Option-B 

Question67:-Which regulation of CEA... Safety Regulations - 2010 governs the maximum interval between supports?         A:-60 

        B:-62 

        C:-33 

        D:-67 

        Correct Answer:- Option-D 

Question68:-Theft of Electricity is specified in which section of the Electricity Act - 2003 

        A:-149 

        B:-135 

        C:-92 

        D:-23 

        Correct Answer:- Option-B 

Question69:-Single phase voltage level specified in Kerala State Electricity Supply Code - 2014 is 

        A:-240 V 

        B:-220 V 

        C:-230 V 

        D:-250 V 

        Correct Answer:- Option-A 

Question70:-Unauthorised use of electricity is specified in which section of the Electricity Act - 2003 

        A:-100 

        B:-58 

        C:-126 

        D:-92 

        Correct Answer:- Option-C 

Question71:-Rural Area specified in Kerala Electricity Supply code - 2014 is an area comprising 

        A:-grama panchayat 

        B:-municipality 

        C:-corporation 

        D:-none of the above 

        Correct Answer:- Option-A 

Question72:-Which is an electrical distribution license in Kerala? 

        A:-Kozhikodu Corporation 

        B:-Kollam Corporation 

        C:-Cochin Corporation 

        D:-Thrissur Corporation 

        Correct Answer:- Option-D 

Question73:-As per Kerala Electricity Supply Code - 2014 he allowable contract demand for a HT consumer based on demand based metering is         A:-2500 KVA 

        B:-3000 KVA 

        C:-5000 KVA 

        D:-6000 KVA 

        Correct Answer:- Option-B 

Question74:-As per the Kerala Electricity Supply Code - 2014 the KW load equivalent to 1 HP is 

        A:-0.75 

        B:-0.735 

        C:-0.746

        D:-0.764 

        Correct Answer:- Option-C 

Question75:-Total allowable load on a power subcircuit is 

        A:-3000 W 

        B:-2000 W 

        C:-5000 W 

        D:-2500 W 

        Correct Answer:- Option-A 

Question76:-The India standard "Guide for safety procedures and practices in electrical work" is         A:-1860 

        B:-2274 

        C:-900 

        D:-5216 

        Correct Answer:- Option-D 

Question77:-The Indian standard "switches for domestic and similar purposes" is 

        A:-3854-1988 

        B:-3481-1966 

        C:-4250-1980 

        D:-3725-1966 

        Correct Answer:- Option-A 

Question78:-What is the minimum statutory horizontal clearance required for a building from an existing  11 kV overhead line?         A:-1.4 m 

        B:-2.3 m 

        C:-1.2 m 

        D:-2 m 

        Correct Answer:- Option-C 

Question79:-What is the device designation number for AC circuit breaker? 

        A:-51 

        B:-52 

        C:-55 

        D:-60 

        Correct Answer:- Option-B 

Question80:-What is the device designation number for an over voltage relay? 

        A:-64 

        B:-53 

        C:-76 

        D:-59 

        Correct Answer:- Option-D 

Question81:-What is the clearance to be provided behind the switch board? 

        A:-2 m 

        B:-40 cm 

        C:-60 cm 

        D:-Either < 20 cm > 75 cm 

        Correct Answer:- Option-D 

Question82:-The energy conservation activities its Kerala is governed by 

        A:-KSEBL 

        B:-Electrical Inspectorate 

        C:-EMC Kerala 

        D:-CEA 

        Correct Answer:- Option-C

Question83:-What is the Average Service Availability Index specified by Kerala State Electricity Regulatory Commission in Urban Areas of Kerala?         A:-98% 

        B:-97.5% 

        C:-95% 

        D:-99% 

        Correct Answer:- Option-A 

Question84:-For parallel operation of transformers one essential condition is 

        A:-Same secondary current 

        B:-Same voltage ratio 

        C:-Same primary current 

        D:-Different percentage impedance 

        Correct Answer:- Option-B 

Question85:-What is the minimum separation distance between an underground telecommunication line and a power cable above 33 kV?         A:-1 m 

        B:-0.6 m 

        C:-0.5 m 

        D:-1.2 m 

        Correct Answer:- Option-B 

Question86:-The section _______________ of the Electricity Act - 2003 insists the rules and regulations to be laid before the parliament.         A:-155 

        B:-149 

        C:-179 

        D:-127 

        Correct Answer:- Option-C 

Question87:-If the fault current exceeds _________________ kA plate earth electrodes shall be used. 

        A:-10 kA 

        B:-6 kA 

        C:-3 kA 

        D:-20 kA 

        Correct Answer:- Option-B 

Question88:-The section _____________ of the Electricity Act - 2003 insists the installation of a correct meter. 

        A:-55 

        B:-148 

        C:-119 

        D:-63 

        Correct Answer:- Option-A 

Question89:-Which section of the Electricity Act 2003 insists the specification of different standards of performance by licence         A:-114 

        B:-61 

        C:-58 

        D:-52 

        Correct Answer:- Option-C 

Question90:-As per which section of the Electricity Act 2003, state government acquire powers to make rules         A:-72 

        B:-6 

        C:-133 

        D:-180 

        Correct Answer:- Option-D 

Question91:-If the transformer capacity is 1000 KVA and above, the secondary side control is 

        A:-moulded case circuit breaker

        B:-miniature circuit breaker 

        C:-switch fuse unit 

        D:-air circuit breaker 

        Correct Answer:- Option-D 

Question92:-What is the minimum front clearance required for a panel having draw out type breaking? 

        A:-1.1 m 

        B:-0.75 m 

        C:-2 m 

        D:-1.5 m 

        Correct Answer:- Option-D 

Question93:-Which section of the Electricity Act 2003 related to the functions and duties of Central Electricity Authority?         A:-180 

        B:-138 

        C:-73 

        D:-25 

        Correct Answer:- Option-C 

Question94:-As per the Kerala Electricity (Intimation of Accident) Rules 2005 an accident should be intimated to the Electrical Inspector in prescribed form with its _____________ hours of the knowledge of the occurance of accidents. 

        A:-48 

        B:-72 

        C:-24 

        D:-12 

        Correct Answer:- Option-A 

Question95:-The form for reporting of electrical accidents involving human beings to Electrical Inspector is ____________.         A:-Form B 

        B:-Form A 

        C:-Form D 

        D:-Form C 

        Correct Answer:- Option-B 

Question96:-The Indian Standard for motor capacitors __________. 

        A:-3553 

        B:-8923 

        C:-13364 

        D:-2993 

        Correct Answer:- Option-D 

Question97:-A gas pressure relay is used in 

        A:-Transformer 

        B:-Motor 

        C:-Capacitors 

        D:-Generator 

        Correct Answer:- Option-A 

Question98:-The capacity of solar power plant is usually specified in 

        A:-KW 

        B:-KWp 

        C:-KVARh 

        D:-KVA 

        Correct Answer:- Option-B 

Question99:-As per CEA... Safety Regulations - 2010 a "linked switch" means a switch unit with all the poles ___________ linked so as to operate simultaneously. 

        A:-electrically 

        B:-electronically

        C:-mechanically 

        D:-none of the above 

        Correct Answer:- Option-C 

Question100:-The differential protection is required for a transformer of capacity _____________, as per CEA... Safety Regulations - 2010.         A:-Less than 10 MVA 

        B:-10 MVA and above 

        C:-1 MVA 

        D:-5 MVA 

        Correct Answer:- Option-B